TDK-Lambda
[II-”fl
....................................
mV (pk»pk)
361-800-526-2324 • www.us.tdk-lambda.com/lp/ Disclaimer: us.tdk-lambda.com/lp/legal.htm
XMS500 Series
Features
ITE & Medical Certifi cations (2 x MOPP)
Class I and Class II operation with Level B EMC
Compact 4 x 7.1” Footprint
Suitable for B and BF Rated Equipment
Five Year Warranty
500W Confi gurable AC-DC Power Supplies
Model XMS500
Input Voltage range 90 - 264VAC (47 - 63Hz)
Inrush Current (Cold start at 264VAC input) A <40A
Hold Up Time (Typ) ms >16ms
Harmonic Compliance - EN/IEC61000-3-2 compliant. 0.97 at 110Vac input
Leakage Current uA <150uA (Class I construction) - See model selector
Touch Current (enclosure leakage) uA <100uA - See model selector
Ripple & Noise mV (pk-pk) <1%
Total Regulation % <2% (Line, load and temperature)
Short Circuit Protection - Hiccup mode, automatic recovery
Overvoltage Protection V Latching (unit shutdown), cycle AC input to reset
Effi ciency % Up to 92% (230VAC input, 100% load)
Operating Temperature °C 0 to +70°C, derate linearly to 50% load from 50 to 70°C. -20°C start-up
Storage Temperature °C -40 to +85°C (+70°C for top fan versions)
Humidity (non condensing) %RH 5 - 95%RH
Cooling - Forced air (500W): 1m/s airfl ow or top mount fan; Convection (250W minimum)(2)
Withstand Voltage VAC Input to Ground 1.5kVAC (1xMOPP) Class I only, Input to Output 4kVAC (2xMOPP),
Output to Ground 1.5kVAC (1xMOPP) Class I only
Insulation Class - Class I or Class II - See model selector
Vibration (non operating) - 10 to 200Hz at 2G. Conforms to IEC610068-2-6, IEC68-2-6
MIL-STD-810G, Method 514.6, Pro I, Cat 4,10
Shock - ±3 x 30g shocks in each plane, total 18 shocks, 30g shock = 11ms (±0.5msec), half sine
Conforms to EN60068-2-27, EN60068-2-47, IEC68-2-27, IEC68-2-47, JIS C0041-1987.
Conforms to MIL-STD-810G, Method 516.6, Pro I, IV
Safety Agency Certifi cations - IEC/EN/UL60950-1 and 60601-1. ANSI/AAMI ES60601-1. Designed to meet IEC61010-1
Altitude m -200 to 5000m operational (3000m for 60601-1) (-200 to 5000m storage/transportation)
Conducted & Radiated EMI - EN55011 / EN55032 Class B, EN60601-1-2:2015 4th Edition
Immunity - EN61000-4-2, -3, -4, -5, -6, -8, -11, -12 and -14, EN60601-1-2:2015 4th Edition
Weight (Typ) g See application notes
Size (WxLxH) Open frame version In (mm) 4 x 7.1 x 1.46” (102 x 180 x 37mm)
Warranty yrs Five years
Connectors - Molex as standard with separate ground faston
See Installation Manual for part numbers
Specifi cations (1)
Key Market Segments & Applications
Note: 1. See website for detailed specifi cations
2. Higher convection rating possible depending on confi guration, mounting orientation, and specifi c application operating